Single Phase Pole Mounted Transformer
Service condition
a) Suitable for both indoor or outdoor
b) Air temperature: Maximum temperature: +40°C; Minimum temperature: -25°C
c) Humidity: Monthly average humidity 95%; Daily average humidity 90%.
d) Altitude above sea level: Maximum installation altitude: 2000m.
e) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
f) No frequent violent shake
Note: * Beyond those service condition should enquiry to manufacturer technical dept during order
Rating Details
General technical information is listed below:
Information on less common requirements can be obtained through Sinoamigo sale department
Capacity kVA: 3kVA --- 167kVA
Temperature rise: 65°C
Cooling type: ONAN
Working Frequency: 50/60Hz
Polarity: additive or Subtractive
Core type: CRGO or Amorphous
Protection: CSP or not
| Primary Voltage | Secondary Voltage | |
| Rating(V) | BIL(kV) | 120V/240V 240V/480V 139V/277V 250V/500V |
| 4160-4800 | 75 | |
| 7200-12470 | 95 | |
| 13200-14400 | 125 | |
| 19920-22900 | 150 | |
| 34500 | 200 | |
| Capacity (kVA) | Primary Rating (V) | Amorphous core | CRGO core | ||
| No load loss (W) | Load loss (W) | No load loss (W) | Load loss (W) | ||
| 3 | 13800/7967 13200/7620 11000/6350 or others | 8 | 45 | 9 | 45 |
| 5 | 8 | 75 | 19 | 75 | |
| 10 | 12 | 120 | 36 | 120 | |
| 15 | 15 | 195 | 50 | 195 | |
| 25 | 18 | 290 | 80 | 290 | |
| 37.5 | 30 | 360 | 105 | 360 | |
| 50 | 32 | 500 | 135 | 500 | |
| 75 | 45 | 650 | 190 | 650 | |
| 100 | 50 | 850 | 210 | 850 | |
| 167 | 65 | 1410 | 350 | 1410 | |